-- PNETMOD-MIB 1.00 -- History: -- 1.00 6. 11.2012 David Chvalkovsky - modified from NSD1800-MIB -- -- This is a MIB for Powernet module PNETMOD-MIB DEFINITIONS ::= BEGIN IMPORTS OBJECT-TYPE FROM RFC-1212 Gauge, enterprises FROM RFC1155-SMI DisplayString, sysName FROM RFC1213-MIB; -- -- Type Definitions -- OnOff ::= INTEGER { off (0), on (1) } OKFail ::= INTEGER { OK (0), Fail (1) } ValueType ::= INTEGER { DI (0), AI (1) } AlarmDescription ::= INTEGER { InputGridFailure (1) , InputFuseFailure (2) , PowerSourceFailure (3) , PowerSourceCurrentOutOfRange (4) , BatteryVoltageOutOfRange (5) , BatteryCurrentChargeOutOfRange (6) , BatteryTemperatureOutOfRange (7) , BatteryFuseFailure (8) , OutputFuseFailure (9) , OutputStateDisconnected (10) } SignedNumber ::= INTEGER (-32758..32757) Index ::= INTEGER (0..255) TimeStamp ::= TimeTicks -- -- Node Definitions -- bke OBJECT IDENTIFIER ::= { enterprises 27533 } pnetMod OBJECT IDENTIFIER ::= { bke 5 } -- grid Group ----------------------------------------------------------------- grid OBJECT IDENTIFIER ::= { pnetMod 1 } gridState OBJECT-TYPE SYNTAX OKFail ACCESS read-only STATUS current DESCRIPTION "Grid State Ok/Fail value" ::= { grid 1 } gridFuse OBJECT-TYPE SYNTAX OKFail ACCESS read-only STATUS current DESCRIPTION "Grid Fuse Ok/Fail value" ::= { grid 2 } -- source Group ---------------------------------------------------------------- powerSource OBJECT IDENTIFIER ::= { pnetMod 2 } powerSourceState OBJECT-TYPE SYNTAX OKFail ACCESS read-only STATUS current DESCRIPTION "Power Source State Ok/Fail value" ::= { powerSource 1 } powerSourceCurrent OBJECT-TYPE SYNTAX SignedNumber ACCESS read-only STATUS current DESCRIPTION "Power Source Current value XXXX divide by 10 to get XXX.X" ::= { powerSource 2 } -- accumulator Group ----------------------------------------------------------- accumulator OBJECT IDENTIFIER ::= { pnetMod 3 } accuVoltage OBJECT-TYPE SYNTAX SignedNumber ACCESS read-only STATUS current DESCRIPTION "Accumulator Voltage value XXXX divide by 10 to get XXX.X" ::= { accumulator 1 } accuCurrent OBJECT-TYPE SYNTAX SignedNumber ACCESS read-only STATUS current DESCRIPTION "Accumulator Current value XXXX divide by 10 to get XXX.X" ::= { accumulator 2 } accuTemperature OBJECT-TYPE SYNTAX SignedNumber ACCESS read-only STATUS current DESCRIPTION "Accumulator Temperature value -XXX divide by 10 to get -XX.X" ::= { accumulator 3 } accuFuse OBJECT-TYPE SYNTAX OKFail ACCESS read-only STATUS current DESCRIPTION "Accumulator Fuse Ok/Fail value" ::= { accumulator 4 } -- output Group ---------------------------------------------------------------- output OBJECT IDENTIFIER ::= { pnetMod 4 } outFuse OBJECT-TYPE SYNTAX OKFail ACCESS read-only STATUS current DESCRIPTION "Output Secure Ok/Fail value" ::= { output 1 } outState OBJECT-TYPE SYNTAX OnOff ACCESS read-write STATUS current DESCRIPTION "Output State On/Off value" ::= { output 2 } -- Alarm Group ----------------------------------------------------------------- alarms OBJECT IDENTIFIER ::= { pnetMod 10 } alarmTable OBJECT-TYPE SYNTAX SEQUENCE OF AlarmEntry ACCESS not-accessible STATUS current DESCRIPTION "A list of input entries." ::= { alarms 1 } alarmEntry OBJECT-TYPE SYNTAX AlarmEntry ACCESS not-accessible STATUS current DESCRIPTION "An entry containing information applicable to a particular input." INDEX { alarmIndex } ::= { alarmTable 1 } AlarmEntry ::= SEQUENCE { alarmIndex Index, alarmDescription AlarmDescription, valueType ValueType, value SignedNumber, alarmTimeStamp TimeStamp } alarmIndex OBJECT-TYPE SYNTAX Index ACCESS read-only STATUS current DESCRIPTION "The input index." ::= { alarmEntry 1 } alarmDescription OBJECT-TYPE SYNTAX AlarmDescription ACCESS read-only STATUS current DESCRIPTION "The input alarm description." ::= { alarmEntry 2 } valueType OBJECT-TYPE SYNTAX ValueType ACCESS read-only STATUS current DESCRIPTION "The input digital or analog type." ::= { alarmEntry 3 } value OBJECT-TYPE SYNTAX SignedNumber ACCESS read-only STATUS current DESCRIPTION "The input alarm value." ::= { alarmEntry 4 } alarmTimeStamp OBJECT-TYPE SYNTAX TimeStamp ACCESS read-only STATUS current DESCRIPTION "The input alarm duration." ::= { alarmEntry 5 } -- Trap Definitions ------------------------------------------------------------ tsTrapAlarmStart TRAP-TYPE ENTERPRISE pnetMod VARIABLES { sysName, alarmDescription, valueType, value } DESCRIPTION "This trap is sent each time an alarm is inserted into the alarm table." ::= 1 tsTrapAlarmEnd TRAP-TYPE ENTERPRISE pnetMod VARIABLES { sysName, alarmDescription, valueType, value } DESCRIPTION "This trap is sent each time an alarm is removed from the alarm table." ::= 2 END